Specifications
| Temperature | Fresh Air, Supply Air, Return Air, Mixed Air, Wall Mounted Temp. Sesnor | 
| Air Humidity | Fresh Air, Supply Air, Return Air, Mixed Air | 
| Compressor Control Stages | 1 Stage Command/Feedback, 2 Stages Command/Feedback, 3 Stages Command/Feedback | 
| Heater Stages | Heater Stage 1 Command/Feedback, Heater Stage 2 Command/Feedback, Heater Stage 3 Command/Feedback | 
| Supply Fan | Start-Stop Command, Run Status, Trip Fault Alarm, Air Flow, Selector Switch Auto, VFD Speed Control, VFD Speed Feedback, Smoke Detector | 
| Return Fan | Start-Stop Command, Run Status, Trip Fault Alarm, Air Flow, Selector Switch Auto, VFD Speed Control, VFD Speed Feedback, Smoke Detector | 
| Filter | HEPA, Pre Filter Status, Bag Filter Status | 
| Damper Actuator | Fresh Air Damper Command/Feedback, Return Air Damper Control/Feedback, Mixing Air Damper Control/Feedback | 
| Humidifier | Start-Stop Command, ON-OFF Status | 
| Recovery Wheel | Start-Stop Command, ON-OFF Status |