BMS Maintenance Services

Standard BMS maintenance service

Maintenance includes:
1- Isnpect active alarms, and verify acknowledgment
2- Inspection of each DDC-workstation connection
3- Check for and install BMS vendor patches and updates
4- Check memory storage capacity in the server
5- Varifing licenese healthy status
6- Varifing and testing time schedules of DDC panels and related equipments

This service doesnt include supply of any material.
Inspection report will be provided including any spare parts required
SR 4,000.00

Proffessional BMS maintenance service

Maintenance includes:
1- Isnpect active alarms, and verify acknowledgment
2- Inspection of each DDC-workstation connection
3- Check for and install BMS vendor patches and updates
4- Check memory storage capacity in the server
5- Varifing licenese healthy status
6- Review alarm routing configuration to approperiate administartive levels
7- Inspection of alarm remote notification confirguration (SMS - Email)
8- Review analogue points alarms thresholds
9- Varifying and testing of critical points alarm
10- Taking backup of the software configuration and historical data
11- Review alarm logs to identify frequently occurring issues and ensure proper alarm acknowledgement
12- Review network performance
13- Varifing and testing time schedules of DDC panels and related equipments
14- Check for physical damage, rust, and dust accumulation, panel cooling/ventilation in panel
15- Inspection of control cables (tightness, labeling, routing)

This service doesnt include supply of any material.
Inspection report will be provided including any spare parts required
SR 7,000.00

Premium BMS maintenance service

Maintenance includes:
1- Isnpect active alarms, and verify acknowledgment
2- Inspection of each DDC-workstation connection
3- Check for and install BMS vendor patches and updates
4- Check memory storage capacity in the server
5- Varifing licenese healthy status
6- Review alarm routing configuration to approperiate administartive levels
7- Inspection of alarm remote notification confirguration (SMS - Email)
8- Review analogue points alarms thresholds
9- Verify that graphical dashboard reference links are mapped correctly and that live data loads correctly
10- Review alarm priority configuration (High - Med - Low)
11- Review of users roles and security groups configuration
12- Test failover systems (backup server, redundancy)
13- Analyze energy consumption trends
14- Varifying and testing of critical points alarm
15- Taking backup of the software configuration and historical data
16- Review alarm logs to identify frequently occurring issues and ensure proper alarm acknowledgement
17- Review network performance
18- Varifing and testing time schedules of DDC panels and related equipments
19- Check for physical damage, rust, and dust accumulation, panel cooling/ventilation in panel
20- Inspection of control cables (tightness, labeling, routing)
21- Varifying and testing operation sequence
22- Testing and inspection of DDC input points values
23- Testing by triggering DDC output points
24- Replace faulty controllers and reprogramming
25- Clean sensor to insure accurate reading
26- Repair or replace actuators/valves/sensors
27- Maintainance of HVAC damper/valve actuator by adding lubricant
28- Tightness of loose damper/valve actuator

This service doesnt include supply of any material.
Inspection report will be provided including any spare parts required
SR 15,000.00